DHA Lahore Fire Safety Requirements (2026) — Houses & Commercial Plazas

Short answer: Under the DHA Construction & Development Regulations 2026 (Regulation 41, Annex C & D), every house from 5 Marla to 2 Kanal and every commercial plaza from 4 to 32 Marla in DHA Lahore must install a wired fire alarm system — control panel at ground floor, smoke/heat detectors in exact quantities per plot size, manual call points, sounders, emergency lights, and DCP/CO2 fire extinguishers. Two rules catch most people out: wireless detectors are not allowed, and all fire system wiring must use fire resistant cable in separate conduits. The exact quantities for your plot size are in the tables below.

DHA is one of the few authorities in Pakistan that publishes exact equipment counts per plot size — which means there is no guesswork about what your house or plaza needs. This guide reproduces those requirements in simple form.

General rules — Regulation 41

Houses — requirements by plot size (Annex C)

Requirement5 Marla8 Marla10 Marla1 Kanal2 Kanal
Smoke/Heat Detectors5 GF + 6 FF8 GF + 6 FF9 GF + 7 FF17 GF + 14 FF37 GF + 29 FF
Basement detectors1 per 150 sq ft — at least 1 in each compartment
Manual Call Points1 per floor1 per floor1 per floor1/floor + 1 servant qtr2/floor + 1 each servant qtr
Fire Alarm Sounders1/floor + 1 garage1/floor + 2 garage1/floor + 2 garage1/floor + servant qtr + 2 garage1/floor + each servant qtr + 2 garage
Emergency Lights1 per floor1 per floor1 per floor2/floor + servant qtr2/floor + each servant qtr
DCP 6KG Extinguishers2 per floor2 per floor2 per floor2/floor + 1 servant qtr3/floor + 1 each servant qtr
CO2 6KG Extinguisher1 per house1 per house1 per house1 + 1 servant qtr1 + servant qtrs
Fire Blankets2222 + 1 servant qtr2 + 1 each servant qtr
First Aid Box1 in each house
Alarm Control PanelClose to main entry/exit at ground floor
KitchenHeat detector: at least 1 per kitchen (+1 per 150 sq ft extra) · Wet chemical extinguisher recommended per kitchen

Commercial plazas — requirements by plot size (Annex D)

Requirement4 Marla6 Marla8 Marla16 Marla32 Marla
Smoke Detectors (per floor, hall/open area)68102040
+ per compartmentAt least 1 in each compartment
Manual Call Points2/floor + 1 stair2/floor + 1 stair3/floor + 1 stair4/floor + 1 stair5/floor + 1 stair
Emergency Exit Lights2/floor + 1 stair2/floor + 1 stair3/floor + 1 stair4/floor + 1 stair5/floor + 1 stair
DCP 6KG Extinguishers2 per floor2 per floor3 per floor4 per floor5 per floor
Emergency ExitCollapsible ladderCollapsible ladderIron/steel staircaseIron/steel staircaseProper emergency staircase
Fire Alarm SoundersAt least 2 per floorAt least 3 per floor
Fire Blankets / First Aid2 each per building3 each per building
Gas Cylinder StorageRooftop, fiber sheet, barricaded, max 36 sq ft (6'×6')Max 64 sq ft (8'×8')

Kitchen, lab and electrical room rules (all plazas)

The two rules everyone misses

1. No wireless detectors. The regulations state plainly: no wireless smoke/heat detectors should be installed. Every detector, sounder and manual call point must be wired to the fire alarm control panel. The cheap battery-operated detectors sold online do not meet DHA requirements.

2. Fire resistant cable only. All fire protection equipment must be installed using fire resistant (FR) cable, run in separate conduits, with the electrical DB close to the main entry/exit at ground floor. Ordinary electrical cable fails this requirement even if the devices are correct.

Building or upgrading in DHA?

HIFAZAT's office is opposite DHA Rahbar Gate-5 on Defence Road — DHA is our home ground. We install complete DHA-compliant wired systems: conventional alarm panel, detectors, MCPs, sounders, extinguishers and FR cabling, matched exactly to your plot size per Annex C/D.

Frequently Asked Questions

Is a fire alarm system mandatory for houses in DHA Lahore?

Yes. Under the DHA Construction & Development Regulations 2026 (Annex C), every house from 5 Marla to 2 Kanal requires a fire alarm control panel near the main entry/exit at ground floor, wired smoke/heat detectors on every floor, manual call points, sounders, emergency lights, DCP and CO2 fire extinguishers, fire blankets and a first aid box. Wireless detectors are not permitted — all devices must be wired to the control panel using fire resistant cable.

How many smoke detectors are required in a 1 Kanal DHA house?

A 1 Kanal house in DHA Lahore requires 17 smoke/heat detectors at ground floor and 14 at first floor, plus 1 per 150 sq ft in the basement, with at least one detector in each compartment. It also requires 1 manual call point per floor plus one in the servant quarter, 2 emergency lights per floor, 2 DCP 6KG extinguishers per floor, 1 CO2 extinguisher, and fire blankets.

What are DHA fire safety requirements for commercial plazas?

Per Annex D of DHA Regulations 2026, commercial plazas require smoke detectors per floor scaled by plot size (6 per floor for 4 Marla up to 40 per floor for 32 Marla), manual call points and emergency exit lights per floor plus staircase, DCP 6KG extinguishers per floor, CO2 and wet chemical extinguishers in kitchens, an illuminated exit sign on each floor, a control panel at ground floor, and an emergency exit — from collapsible ladder (4–6 Marla) to a proper emergency staircase (32 Marla).

Are wireless smoke detectors allowed in DHA Lahore?

No. DHA Regulations 2026 explicitly state that no wireless smoke or heat detectors should be installed. All detectors must be connected to the fire alarm control panel along with sounders and manual call points, and the wiring must use fire resistant cable run in separate conduits.

Can HIFAZAT install a DHA-compliant fire safety system?

Yes. HIFAZAT's office is located on Defence Road opposite DHA Rahbar, and we install DHA-compliant systems across DHA Lahore: wired conventional fire alarm panels, smoke and heat detectors, MCPs, sounders, DCP/CO2/wet chemical extinguishers, fire blankets and emergency lights — with fire resistant cable as the regulations require. Call or WhatsApp 0309-1666636.

Note: This guide summarizes the fire safety provisions of the DHA Construction & Development Regulations 2026 (Regulation 41, Annex C and Annex D) in simplified form for general awareness. Requirements are applied per your building's approved plan — verify specifics with DHA and confirm your building's exact needs through a site inspection.